28
CtrL
Control mode
onoF: on-off control. For situation not requiring high precision
APId: advanced artificial intelligence PID control. (Recommended)
nPId: standard PID algorithm with anti integral-saturation function (no integral when
PV-SV > proportional band)
POP: Transmit PV. The instrument works as a temperature re-transmitter.
SOP: Transmit SV. The instrument works program generator.
onoF
APId
nPId
POP
SOP
Srun
Running Status
run: Control or program was running, RUNled light on
S t o P : Control or program was stopped. Lower display keep flashing S t o P and
RUNled light off.
HoLd: This only functioned on AI-526P, this will keeping temperature when this HoLd
was appeared. If the parameter Pno=0(Non timing limitation mode), controller will
functioning same at AI-526, if Pno>0 (in program mode),and Srun was set asHoLd,
means the timer s t o p s and the temperature remains; user can resume the timer by
pressing the Holdfrom panel.
S t o P /
run /
HoLd