The 2
nd
proportional band in PID and APID control. Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can obtained by auto tuning. They can also be
manually inputted if you already know the correct values.
No integral effect when I=0
No derivative effect when d=0
Same description and function as parameter as “Ctl”
CHYS is used for on-off control to avoid frequent on-off action of relay.
For a reverse acting (heating) system, when PV > SV, output turns off; when
PV<SV-CHYS, output turns on.
For a direct acting (cooling) system, when PV<SV, output turns off; when
PV>SV+CHYS, output turns on.