EN.
45
Parameter no. 73 Slats position
Choose the position of the slats after up/down movement (activated through the Z-Wave
controller or the push-buttons) is completed.
Values (data type is 1 byte dec):
default value 1
0 - Slats return to the previously set position only after being activated via the Z-Wave
controller (not valid for limit switch positions).
1 - Slats return to the previously set position in case they were activated via the Z-Wave
controller, push-button operation or when the lower limit switch is reached.
Parameter no. 74 Motor moving up/down time
This parameter defines the time, required by the Shutter motor, to completely open or
completely close the attached shutters.
Values (data type is 2 byte dec):
default value 0
0 moving time disabled (working with limit switches)
1 - 32767 = 0.1seconds 3276.7 seconds
After the set time passes, the motor stops (relay goes to the off state).
NOTE: It is important that the reference position, for setting the moving time, is always when
the Shutter is at its lowest position!
Set parameter 74 to 0 and move the Shutter (using the up/down push-buttons or the main
controller UI) to the lowest desired position. When the Shutter reaches this position, set the
parameter 74 to the duration, required by the Shutter, to completely open or completely close