Parameter no. 78 - Forced Shutter calibration
By changing the value of this parameter from 0 to 1, the Shutter enters the calibration mode.
For further information about the calibration process, please see section 9.
Values (data type is 1 byte dec):
default value 0
1 - Start the calibration process. When the calibration process finishes
(completing the full cycle - up, down and up again), set the value of the
parameter 78 (Forced Shutter calibration) back to 0.
Parameter no. 85 Power consumption max delay time
Define the maximum time before the power consumption of the motor, after one of the relays
is switched ON, is read from the device. If there is no power consumption during the set time
(motor not connected, damaged or requires longer time to start, motor at the end position),
the relay will switch OFF. This time is defined by entering it manually.