NOTE:
•
The maximum DC voltage would be 825Vdc, the DC power cable be used
should be able to withstand at least 1000V and required safe ampere
capacity.
•
Please note and confirm that all installation assemblies must comply with
national safety standard and codes.
•
The max. allowable distance between the power cabinet and the dispenser
is 30m.
•
The power cabinet and the distribution box are recommended to keep
distance from the end users to have better operation experience.
•
The similar design concept in appearance is recommended to the power
cabinet and the distribution box.
•
Must use the CAT6A SFTP cable 24AWG or 26AWG with CAT6A FTP RJ45
Plug or higher-level cable/Plug increased shielding for ethernet contact.