ZXA10C300CabinetInstallationGuide(19Inch)
ThelightningprotectiondesignforthecableinletsonthecabinetmustconformtoLevelC
andDstandard.-48Vterminalisequippedwitha20kAlightningprotectiondevice.The
lightningprotectiondesignforoutgoingusercables,E1cables,andEthernetcablesmust
conformtoLevelDlightningprotectionstandard.
C.3LightningProtectionGroundinginCentralOfce
Takethefollowingconsiderationswhenimplementingthelightningprotectiongroundingof
thepowersystemsintheCentralOfce:
lLaytheACpowercableundergroundatadepthofmorethan15meters.
lInstallLevelBlightningprotectiondevicewiththeACdistributioncard.Connectthe
protectiondevicegroundingtothehorizontalgroundingbar.
lInstallLevelClightningprotectiondeviceintheDCdistributioncabinetinthepower
supplysystemroom.Connecttheprotectiondevicegroundingtothehorizontal
groundingbar.
lInstallLevelDlightningprotectiondeviceintherectier.Connecttheprotectiondevice
groundingtothehorizontalgroundingbarthroughtheDCdistributioncabinet.
C.4LightningProtectionGroundinginRemoteOfce
Takethefollowingconsiderationswhendesigningthelightningprotectiongroundingofthe
powersystemsinaRemoteOfce:
lLaytheACpowercableundergroundatadepthofmorethan15meters.
lSinceboththeACdistributioncardandDCdistributioncabinetareinsameequipment
room,thedistancebetweenLevelBlightningprotectiondeviceandLevelClightning
protectiondevicemustmeettherequirementsofdecouplingdistance.
lIftheprotectiongroundingcableisarrangedseparately,thedistancebetweenLevel
BlightningprotectiondeviceandLevelClightningprotectiondeviceintheDC
distributioncabinetshouldbemorethan5meters.
lIftheprotectiongroundingcableisarrangedinparallelwiththepowercable,the
distancebetweenLevelBlightningprotectiondeviceandLevelClightningprotection
deviceintheDCdistributioncabinetshouldbemorethan15meters.
lIftheconditiondoesnotmeettherequirements,installadecouplinginductance
(calculateby1.5µH/m)infrontofLevelClightningprotectiondevice.
lConnectLevelBlightningprotectiondeviceinstalledonACdistributioncardtothe
protectiongroundingbarintheequipmentroom.
lConnectLevelClightningprotectiondeviceinstalledonDCdistributioncabinettothe
protectiongroundingbarintheequipmentroom.
lConnectLevelDlightningprotectiondevice,installedonrectiertotheDCdistribution
cardandthentotheprotectiongroundingbarintheequipmentroom.
lConnect-48VgroundingoftheDCpowerdistributioncabinettoworkinggrounding
bar.Ifthereisnoworkinggroundingbar,connectittotheprotectiongroundingbar.
lForthegroundingcableoftheACdistributioncardequippedwithLevelBlightning
protectiondevice,useamulti-copperwire(≥35mm
2
).
C-2
SJ-20110909101511-005|2011-12-31(R1.1)ZTEProprietaryandCondential