ZXA10C300CabinetInstallationGuide(19Inch)
àBindcablesintoughstightlyandstraightly.Fixcablesatturningsoroutletswith
plasticclips.
lPowercableandgroundingcableinspectionincludesthefollowing:
àThespecicationsofpowercablesandgroundingcablesmustmeetthedesign
requirements.
àThepowercableandgroundingcablemustbeone-piececablewithoutanyjoints.
àLaythepowercableandgroundingcableseparatelyfromothercables.
àConnecttheprimarypowertothepowerterminalsonthecabinet.Makesurethat
thepositiveandnegativepolaritiesareconnectedproperly.
ShelfPowerSupplyInspection
Shelfpowersupplyinspectionincludesthefollowing:
lChecktheshelfpowercablevoltagewithamultimeter.Makesurethattheshelfpower
cablevoltagemeetsthepowersupplyrequirements.
lPowerONthepowercardtochecktheshelfpowersupply.
lCheckthebackplanepowersupply.
CardPowerSupplyInspection
Cardpowersupplyinspectionincludesthefollowing:
lCheckwhetherthecardiscorrectlyinserted.
lPowerONthepowercardtocheckthecardpowersupply.
6.2Power-ON/OFFInspection
Thistopicincludesthefollowing:
lInspectionBeforePower-ON
lPower-ONProcess
lPower-OFFProcess
6.2.1InspectionbeforePower-ON
Overview
Afterinstallingthecabinetsuccessfully,conductpower-ONtest.Checkandconrmthe
internalandexternalstatusoftheequipmentbeforepower-ON.
Temperature,Humidity,andVoltageCheck
Thetemperature,humidity,andvoltagecheckincludesthefollowing:
lTemperature:-5to45
lRelativehumidity:10%90%
lDCvoltage:-57VDCto-41VDC
6-2