E-BUS Digital Room Sensor Technical Guide 3
OVERVIEW
Overview
The E-BUS Digital Room Sensors are used to sense Space Temperature
only or Space Temperature & Space Humidity. See Figures 1 & 2.
The ASM01819 is the Space Temperature Sensor only model and the
ASM01820 & ASM02221 are a combination Space Temperature & Space
Humidity Sensor model. The ASM02221 model includes an enclosure
without LCD display, front LEDs, and buttons.
Any of the sensors can be used with the VCCX2 Controller and VCB-X
Controller and connect to the controller using various lengths of EBC
E-BUS cables connected between the controller and the sensor. The
EBC E-BUS cables should not run in conduit with other AC line voltage
wiring or with any conductors carrying highly inductive loads.
The ASM01819 model can be used with the VAV/Zone Controller. It is
either hard-wired or connected via EBC E-BUS cable.
The ASM01819 & ASM01820 sensors provide the following useful
functions:
Provides 112 x 64 monochrome Graphical LCD display with
LED backlight
Displays the Current Space Temperature
Displays Outdoor Air Temperature (if controller is confi gured
with an OA Temperature Sensor)
Features
Figure 1: ASM01819 & ASM01820 E-BUS Digital
Room Sensor with LCD Display and Buttons
Display
Override
OVERRIDE
ALARM
Displays the Current Space Humidity (ASM01820 model
only)
Displays Outdoor Air Relative Humidity (ASM01820 model
if controller is confi gured with an OA Humidity Sensor)
Displays the Current Zone Setpoint Temperature when slide
adjust is entered
Equipped with Push Buttons for changing the Zone Setpoint
Temperature
Equipped with an Override Button for forcing the VAV/Zone
Controller or VCCX2 / VCB-X Controller into Occupied
Operation from Unoccupied Operation
Provides graphics to indicate the Mode of Operation
Allows connection of a remote 10K Ohm, Type III thermistor
temperature sensor (or 4 sensor averaging array). See
Connecting a Remote Sensor section in the Appendix on
page 15 for details.
Provides LEDs to indicate Schedule Override, Button Push,
Alarms, and Communications
Can display Temperature reading from a Remote Temperature
Sensor (see Figures 21 & 22, pages 15 & 16 for instructions)
Figure 2: ASM02221 E-BUS Digital Room Sensor -
No LCD Display or Buttons