Manual Corrigo Ventilation, revision R Chapter 17 Configuration 95
Alarm text Pri Description
30 Fire damper is out of
operation
B Fire damper exercise test failed
31 Supply Air Fan control error - Supply air pressure deviates too much from
the setpoint for too long.
32 Extract Air Fan control error - Extract air pressure deviates too much from
the setpoint for too long.
33 Supply Air Fan external
operation
C SAF run-signal received when unit is
stopped
34 Extract Air Fan external
operation
C EAF run-signal received when unit is
stopped
35 Ventilation Manual mode C The unit is in manual mode
36
Manual supply air control
C
Supply air temp controller in manual control
37
Manual supply Air Fan mode
C
Supply air fan in manual control
38
Manual Supply Air
C
The SAF is in manual mode
39 Manual Extract Air Fan mode C Extract air fan in manual control
40 Manual Extract Air C The EAF is in manual mode
41 Manual Heater Control C The heater is in manual mode
42 Manual exchanger control C Heat exchanger output in manual control
43
Manual cooler control
C
Cooling output in manual control
44
Manual P1-Heater
C
Heating circulation pump in manual control
45 Manual P1-Exchanger C Exchanger circulation pump in manual
control
46
Manual P1-Cooler
C
Cooling circulation pump in manual control
47
Fire damp. Manual
C
Fire dampers in manual control
48 Internal battery error A Internal battery needs replacing
49 Sensor error Supply Air temp B Malfunction of connected sensor
50 Sensor error Extract Air temp B Malfunction of connected sensor
51 Sensor error Room temp 1 B Malfunction of connected sensor
52
Sensor error Room temp 2
B
Malfunction of connected sensor
53
Sensor error Exhaust air temp
B
Malfunction of connected sensor
54
Sensor error Extra sensor
B
Sensor error Extra sensor 1
55 Sensor error SAF pressure B Malfunction of connected sensor
56 Sensor error EAF pressure B Malfunction of connected sensor
57 Sensor error Deicing temp B Malfunction of connected sensor
58 Sensor error Frost Protection
temp
B Malfunction of connected sensor
59 Sensor error CO
2
B Malfunction of connected sensor
60 Sensor error Humidity Room B Malfunction of connected sensor
61 Sensor error Humidity Duct B Malfunction of connected sensor
62 Sensor error Extra unit temp B Malfunction of connected sensor
63 Sensor error External control
SAF
B Malfunction of connected sensor
64 Sensor error External control
EAF
B Malfunction of connected sensor
65 Sensor error SAF Pressure 2 B Malfunction of connected sensor
66 Sensor error Humidity
outdoor
B Malfunction of connected sensor