Manual Corrigo Ventilation, revision R Chapter 17 Configuration 95
Alarm text Pri Description
30 Fire damper is out of
B Fire damper exercise test failed
31 Supply Air Fan control error - Supply air pressure deviates too much from
the setpoint for too long.
32 Extract Air Fan control error - Extract air pressure deviates too much from
the setpoint for too long.
33 Supply Air Fan external
C SAF run-signal received when unit is
34 Extract Air Fan external
operation
C EAF run-signal received when unit is
stopped
35 Ventilation Manual mode C The unit is in manual mode
Manual supply air control
Supply air temp controller in manual control
Manual supply Air Fan mode
Supply air fan in manual control
The SAF is in manual mode
39 Manual Extract Air Fan mode C Extract air fan in manual control
40 Manual Extract Air C The EAF is in manual mode
41 Manual Heater Control C The heater is in manual mode
42 Manual exchanger control C Heat exchanger output in manual control
Cooling output in manual control
Heating circulation pump in manual control
45 Manual P1-Exchanger C Exchanger circulation pump in manual
control
Cooling circulation pump in manual control
Fire dampers in manual control
48 Internal battery error A Internal battery needs replacing
49 Sensor error Supply Air temp B Malfunction of connected sensor
50 Sensor error Extract Air temp B Malfunction of connected sensor
51 Sensor error Room temp 1 B Malfunction of connected sensor
Malfunction of connected sensor
Sensor error Exhaust air temp
Malfunction of connected sensor
Sensor error Extra sensor
Sensor error Extra sensor 1
55 Sensor error SAF pressure B Malfunction of connected sensor
56 Sensor error EAF pressure B Malfunction of connected sensor
57 Sensor error Deicing temp B Malfunction of connected sensor
58 Sensor error Frost Protection
B Malfunction of connected sensor
59 Sensor error CO
B Malfunction of connected sensor
60 Sensor error Humidity Room B Malfunction of connected sensor
61 Sensor error Humidity Duct B Malfunction of connected sensor
62 Sensor error Extra unit temp B Malfunction of connected sensor
63 Sensor error External control
SAF
B Malfunction of connected sensor
64 Sensor error External control
B Malfunction of connected sensor
65 Sensor error SAF Pressure 2 B Malfunction of connected sensor
66 Sensor error Humidity
B Malfunction of connected sensor