sym Error HMI code Description Possible Cause Suggested Actions
Primary Variable Out of Range S050.010 Process value is outside its working range The measured pressure value is beyond its Low or High scaling limits
Adjust the working range if 
possible.
Static Pressure Out of Range S048.011 Static Pressure is outside its working range The Measured Static Pressure is beyond its Low  or high scaling limits
Adjust the working range if 
possible.
PILD Output
Both Impulse Lines 
Plugged
M018.038
PILD algorithm has detected both impulse 
lines plugged.
Both connections between the pressure sensor and the process are blocked 
either by plugging or closed valves.
Check valves and impulse line. 
Clean impulse line if necessary 
and initiate PILD training
Impulse Line on High 
Side Plugged
PILD algorithm has detected a plugged 
impulse line on the HIGH side.
The connection between the pressure sensor and the process on the HIGH 
side is blocked either by plugging or closed valves.
Impulse Line on Low 
Side Plugged
PILD algorithm has detected a plugged 
impulse line on the LOW side.
The connection between the pressure sensor and the process on the LOW 
side is blocked either by plugging or closed valves
One Undefined 
impulse line plugged
PILD algorithm has detected one plugged 
impulse line.
One of the connections between the pressure sensor and the process is 
blocked either by plugging or closed valves.
PILD Changed Operating Conditions M016.039
The pressure value currently detected is too 
different from what used for the PILD Training
Process conditions have changed to an extent that new settings for the PILD 
algorithm are needed.
A new Training is necessary for 
this new process condition