Table 75. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF) main settings
Parameter Function Value (Range) Step
High operate value TR2PTDF 500...3000 %Ir 10
Low operate value TR2PTDF 5...50 %Ir 1
Slope section 2 TR2PTDF 10...50% 1
End section 2 TR2PTDF 100...500 %Ir 1
Restraint mode TR2PTDF 5 = Waveform
6 = 2.h + waveform
8 = 5.h + waveform
9 = 2.h + 5.h + wav
-
Start value 2.H TR2PTDF 7...20% 1
Start value 5.H TR2PTDF 10...50% 1
Operation TR2PTDF 1 = on
5 = off
-
Winding 1 type TR2PTDF 1 = Y
2 = YN
3 = D
4 = Z
5 = ZN
-
Winding 2 type TR2PTDF 1 = Y
2 = YN
3 = D
4 = Z
5 = ZN
-
Zro A elimination TR2PTDF 1 = Not eliminated
2 = Winding 1
3 = Winding 2
4 = Winding 1 and 2
-
Table 76. Numerically stabilized low-impedance restricted earth-fault protection (LREFPNDF)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz
±2.5% of the set value or ±0.002 x In
Start time
60, 61
IFault = 2.0 × set Operate value Minimum Typical Maximum
37 ms 41 ms 45 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in denite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5, …
Table 77. Stabilized restricted earth-fault protection (LREFPNDF) main settings
Parameter Function Value (Range) Step
Operate value LREFPNDF 5...50 %In 1
Minimum operate time LREFPNDF 40...300000 ms 1
Restraint mode LREFPNDF 1 = None
2 = Harmonic
-
Start value 2.H LREFPNDF 10...50% 1
Operation LREFPNDF 1 = on
5 = off
-
60 Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
61 Includes the delay of the signal output contact