27. Functions, codes and symbols
Table 103. Protection
Function IEC 61850 IEC 60617 IEC-ANSI
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1 3I> (1) 51P-1 (1)
Three-phase non-directional overcurrent
protection, high stage
PHHPTOC1 3I>> (1) 51P-2 (1)
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1 3I>>> (1) 50P/51P (1)
Three-phase directional overcurrent protec-
tion, low stage
DPHLPDOC1 3I> -> (1) 67-1 (1)
Three-phase directional overcurrent protec-
tion, high stage
DPHHPDOC1 3I>> -> (1) 67-2 (1)
Non-directional earthfault protection, low
stage
EFLPTOC1 Io> (1) 51N-1 (1)
Non-directional earthfault protection, high
stage
EFHPTOC1 Io>> (1) 51N-2 (1)
Non-directional earthfault protection,
instantaneous stage
EFIPTOC1 Io>>> (1) 50N/51N (1)
Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)
Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Admittance-based earth-fault protection EFPADM1 Yo> -> (1) 21YN (1)
Wattmetric-based earth-fault protection WPWDE1 Po> -> (1) 32N (1)
Transient/intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
Non-directional (crosscountry) earth-fault
protection, using calculated Io
EFHPTOC1 Io>> (1) 51N-2 (1)
Negative-sequence overcurrent protection NSPTOC1 I2> (1) 46 (1)
Phase discontinuity protection PDNSPTOC1 I2/I1> (1) 46PD (1)
Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1)
Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)
Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)
Positive-sequence undervoltage
protection
PSPTUV1 U1< (1) 47U+ (1)
Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)
Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)
Distance protection DSTPDIS Z< (1) 21P, 21N (1)
Three-phase underimpedance protection UZPDIS Z<G (1) 21G (1)
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1 3Ith>F (1) 49F (1)
Circuit breaker failure
protection
CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)
Three-phase inrush detector INRPHAR1 3I2f> (1) 68 (1)
Switch onto fault CBPSOF1 SOTF (1) SOTF (1)
Master trip TRPPTRC1 Master Trip (1) 94/86 (1)
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
Multipurpose protection MAPGAPC1 MAP (1) MAP (1)
Fault locator SCEFRFLO1 FLOC (1) 21FL (1)
Reverse power/directional overpower
protection
DOPPDPR1 P>/Q> (1) 32R/32O (1)
Multifrequency admittance-based earth-
fault protection
MFADPSDE1 Io> ->Y (1) 67YN (1)