EasyManua.ls Logo

ABB ABILITY SSC600 - Logging Out

ABB ABILITY SSC600
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TITLETEXTFRAME
Product Guide 1MRS758725
SSC600
Product version: 1.0
30
ABB
Characteristic Value
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
RMS: No suppression
Table 95. Sequence voltage measurement (VSMSQI)
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz At voltages in
range 0.01…1.15 × Un
±1.0% or ±0.002 × Un
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Table 96. Three-phase power and energy measurement (PEMMXU)
Characteristic Value
Operation accuracy At all three currents in range 0.10…1.20 × In
At all three voltages in range 0.50…1.15 × Un
At the frequency fn ±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy
67
±1.5% for reactive power Q and reactive energy
68
±0.015 for power factor
Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Table 97. Frequency measurement (FMMXU)
Characteristic Value
Operation accuracy ±5 mHz
(in measurement range 35...75 Hz)
21. Other functions
Table 98. Pulse timer (PTGAPC)
Characteristic Value
Operation accuracy ±1.0% of the set value or ±20 ms
Table 99. Time delay off (8 pcs) (TOFGAPC)
Characteristic Value
Operation accuracy ±1.0% of the set value or ±20 ms
Table 100. Time delay on (8 pcs) (TONGAPC)
Characteristic Value
Operation accuracy ±1.0% of the set value or ±20 ms
67 |PF| >0.5 which equals |cos φ | >0.5
68 |PF| <0.86 which equals |sin φ | >0.5

Other manuals for ABB ABILITY SSC600