24. Tools
The protection device is delivered as a precongured unit. The de-
fault parameter setting values can be changed from the frontpanel
user interface (local HMI), the Web browser based user interface
(Web HMI) or Protection and Control IED Manager PCM600 in
combination with the IED-specic connectivity package.
PCM600 offers extensive IED conguration functions. For exam-
ple, depending on the protection IED, the IED signals, application,
graphical display and single-line diagram, and IEC 61850 com-
munication, including horizontal GOOSE communication, can be
modied with PCM600.
When the Web HMI is used, the protection device can be ac-
cessed either locally or remotely using a Web browser (Internet
Explorer). The Web HMI functionality can be limited to read-only
access. Local control from Web HMI is possible only when the
device is accessed from the local Web HMI Ethernet port.
Table 101. Tools
Description Version
PCM600 2.9 or later
Web browser Internet Explorer 8.0, 9.0, 10.0 and 11.0
SSC600 Connectivity Package 1.0 or later
Table 102. Supported functions
Function Web HMI PCM600
Device parameter setting
Saving of device parameter settings in the device
Signal monitoring
Disturbance recorder handling
Alarm LED viewing
Access control management
device signal conguration (Signal Matrix) -
Saving of device parameter settings in the tool -
Disturbance record analysis -
XRIO parameter export/import
Graphical display conguration -
Application conguration -
IEC 61850 communication conguration, GOOSE (com-
munication conguration)
-
Phasor diagram viewing -
Event viewing
Saving of event data on the user’s PC
Online monitoring -
• = Supported
25. Cyber security
The device supports role based user authentication and authori-
zation. It can store 2048 audit trail events to a nonvolatile memory.
The non-volatile memory is based on a memory type which does
not need battery backup or regular component exchange to
maintain the memory storage. FTP and Web HMI use TLS encryp-
tion with a minimum of 128 bit key length protecting the data in
transit. In this case the used communication protocols are FTPS
and HTTPS. All rear communication ports and optional protocol