Programming
Page 5-12 ABB Control - AC 31
1SBC 260400 R1001-b 06.99
4.1.4. Initialization /Internal bits backup
Value n to choose Internal bits backed up Internal bits initialized
n = 0 (default value) no backup M 000.00...M 099.15
M 230.00 M 255.15
n = 1...99 M 000.00...M n-1.15 M n.00...M 099.15
M 230.00...M 255.15
n = 100...229 M 000.00...M 099.15 M 230.00...M 255.15
n = 230...254 M 000.00...M 099.15
M 230.00...M n-1.15
M n.00...M 255.15
n < 0, n > 254 M 000.00...M 099.15
M 230.00...M 254.15
M 255.00...M 255.15
Comments:
The bits M 255.00 to M 255.03 are oscillator variables which always start at 0.
The bits M 255.10 to M 255.14 are reserved for the diagnosis.
The M 255.15 bit cannot be backed up and is always reset to 0 at the launch of any
program. Consequently, it may be used to detect the first program cycle.
4.1.5. Initialization / Internal words backup
Value n to choose Internal words backed up Internal words initialized
n = 0 (default value) no backup MW 000.00...MW 099.15
MW 230.00...MW 239.15
MW 255.00...MW 255.15
n = 1...99 MW 000.00...MW n-1.15 MW n.00...MW 099.15
MW 230.00...MW 239.15
MW 255.00...MW 255.15
n = 100...229 MW 000.00...MW 099.15 MW 230.00...MW 239.15
MW 255.00...MW 255.15
n = 230...255 MW 000.00...MW 099.15
MW 230.00...MW n-1.15
MW n.00...MW 255.15
n < 0, n > 255 MW 000.00...MW 099.15
MW 230.00...MW 239.15
MW 255.00...MW 255.15
no initialization