EasyManua.ls Logo

ABB AC 800M

ABB AC 800M
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MBP power and line length calculation Section 2 Transmission Technology
36 3BDS009029R5001 B
MBP power and line length calculation
The distribution of stations on the PROFIBUS PA segment can have a negative
effects on the maximum possible line length in certain circumstances. The following
example is intended to clarify this point:
The case in question is an Ex application. The result of the current calculation is that
a maximum direct current including I
FDE
of 100 mA is flowing. Type A cable is
being used with a resistance coating of 44 Ohm/km.
A requirement for a PROFIBUS PA slave to be able to function properly is that the
input voltage on the bus line must be at least 9 V. The following therefore applies to
the maximum voltage drop over the lead:
U
Lmax
= U
out
- 9 V
Currently U
out
for LD 800P with an Ex interface PL 890 is at least 12.8 V (12.8 V ...
13.4). For the worst case consideration, U
out
should be set to 12.8 V. This results in:
U
Lmax
= 12.8 V - 9 V = 3.8 V
Since all stations are connected at the end of the line, the maximum line resistance
must be
R
L
= U
L
/i
max
R
L
= 3.8 V / 100 mA = 38 Ohm
Figure 5. Voltage calculation and line length
Linking
Device/
R
L
R
L
= Line resistance of line segment x
I
x
= Current consumption of PA station x
i
1
i
2
i
n
> 9 V
U
L
U
out
i
max
Power
Link
Module

Table of Contents

Other manuals for ABB AC 800M

Related product manuals