Section 6 Program Code Issues Alarm and Event Handling
3BSE042835-600 99
InteractionPar.InhXAct In Bool Same as InhXAct but controlled
from faceplate. Only introduced for
a selection of objects.
When declaring the data type for
InteractionPar, the InhXAct
component must be declared with
the attribute “retain”.
X Out Bool Indicates active condition X. This
output is enabled as long as
AEConfigX <> 0. Example: GTH.
XStat Out Bool Indicates active condition X. This
output can be controlled via
Enable.
XEnabled Out Bool Indicates that the XStat and XAct
parameters are enabled. This
parameter can be used when
additional actions should be
performed at Enable/Disable.
XAct Out Bool Indicates active condition X. This
output can be controlled via
Enable and Inhibit.
XActInh Out Bool Indicates that the XAct parameter
is inhibited, either from faceplate or
code. This parameter can be used
when additional actions are
wanted at Inhibit. Only introduced
for a selection of objects.
Table 13. Summary of Alarm and Event parameters (Continued)