Thick Cable Section 2 Transmission Media and Components
24 9ARD000015-600
DCR - @ 20° C 6.9 Ohms/1000 ft (maximum)
Attenuation 0.13 db/100 ft @ 125 kHz (maximum)
0.25 db/100 ft @ 500 kHz (maximum)
Table 7. Physical Characteristics of DC Power Specification for Thick Cables
Physical Characteristics Specification
Conductor pair Size #15 Copper (minimum); 19 strands
minimum (individually tinned)
Insulation diameter 0.098 inches (nominal)
Colors Red
Black
pair/Twist/ft 3 (approximately)
Tape shield over pair 1.0 mil/ 1 mil, Al/Mylar
Al side out w/shorting fold (pull-on applied)
Table 8. Electrical Characteristic of DC Power Specification for Thick Cables
Electrical Characteristic Specification
DCR - @ 20° C (68° F) 3.6 Ohms/1000 ft (maximum)
Table 6. Electrical Characteristics of Data Pair Specification for Thick Cables (Continued)