Chapter 3 – Electrical Installation 
3-38  ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
Installation of 
Optional Modules
This section gives general installation instructions for the DriveWindow 
PC tool and ACx 600 optional modules, such as fieldbus adapters, I/O 
extension modules and the pulse encoder interface. Connection 
examples are given at the end of the section.
Placement The module should be installed on the DIN mounting rail inside the 
inverter unit cabinet, located on the inside of the left-hand side cabinet 
wall. The DIN rail of ACx 6x7 units is located in the Auxiliary Control 
Unit (ACU). Follow the instructions given in the Mechanical Installation 
chapter of the module manual.
Power Supply
for the Module
The 24 V d.c. supply for one optional module is provided by the NIOC 
board of the inverter module (terminal X23). The NIOC board is 
assembled into the NDCU control unit, mounted on a DIN rail inside the 
inverter unit cabinet or in the Auxiliary Control Unit (ACx 6x7 units).
Fibre Optic Link Optional modules are connected via a DDCS fibre optic link to the 
NAMC board or NDCO board (both mounted on top of the NIOC 
board). The terminals to which the cables are connected on the NAMC/
NDCO board are given in the table below. Channel CH1 is on 
NAMC-11/51 board. Channels CH0, CH2 and CH3 are on the NDCO 
board. The NAMC-03 and NAMC-21/22 boards include channels CH0 
to CH3.
The NAMC 11/51 board is used with ACx 6x7 units. The NAMC-21 and 
NAMC 22 boards are used with ACS 600 MultiDrive: NAMC-21 with 
AC 80 and NAMC 22 with the fieldbus.
 
* on the NDCO board when the NAMC-11/51 board is used. 
1)
 DriveWindow Light is connected via an NPCU RS-232/485 converter to the panel 
connector on the cover (or to modular jack X19 on the NAMC-11/51 board). 
Module Type Channel Termi n als
Fieldbus Adapter Modules CH0* V13*, V14*
I/O Extension Modules CH1 V15, V16
Pulse Encoder Interface Module CH2* with ACS 600 
Standard Application 
Program 5.x
V17*, V18*
CH1 with ACS 600 System, 
Crane Master/Follower and 
Template Application 
Program
V15, V16
Double Pulse Encoder Interface 
Module (for ACP 600 only)
CH2* V17*, V18*
DriveWindow 
1)