ACH550-UH User’s Manual 1-191
Embedded fieldbus
5309 EFB STATUS This parameter indicates the internal status of the EFB
Protocol as follows:
• IDLE – EFB Protocol is configured but not receiving
messages.
• TIMEOUT – Time between valid messages has
exceeded the interval set by parameter 3019.
• OFFLINE – EFB Protocol is receiving messages NOT
addressed to this drive.
• ONLINE – EFB Protocol is receiving messages
addressed to this drive.
• RESET – EFB Protocol is in reset.
• LISTEN ONLY – EFB Protocol is in listen-only mode.
5310 EFB PAR10 Not used
for Comm
setup.
Sets the response turnaround time in
milliseconds in addition to any fixed delay
imposed by the protocol. When this protocol is
selected, the default value is:
3 ms 0 ms 5 ms
5311 EFB PAR11 Not used for Comm setup. This parameter, together
with parameter 5317, EFB
PAR 17, sets BACnet
Device Object Instance
IDs:
• For the range 1 to
65,535: This
parameter sets the ID
directly (5317 must be
0). For example, the
following values set
the ID to 49134: 5311
= 49134 and 5317 = 0.
• For IDs > 65,335: The
ID equals 5311’s value
plus 10,000 times
5317’s value. For
example, the following
values set the ID to
71234: 5311 = 1234
and 5317 = 7.
5314 EFB PAR14 Not used for Comm setup.
5315 EFB PAR15 Not used for Comm setup.
5316 EFB PAR 16 Not used for Comm setup. This parameter indicates
the count of MS/TP tokens
passed to this drive.
Code Description
EFB Protocol Reference
Modbus N2 FLN BACnet