ACH550-UH User’s Manual 1-221
Embedded fieldbus
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets { } may be unbundled at the field panel.
Detailed point descriptions
{91} LAI PREV FAULT 1 - - 1 0 - -
{92} LAI PREV FAULT 2 - - 1 0 - -
{93} LDI OK.FAULT OK - 1 0 FAULT OK
{94} LDO RESET FAULT NO - 1 0 RESET NO
{95} LAO MBOX PARAM - - 1 0 - -
{96} LAO MBOX DATA - - 1 0 - -
{97} LDO MBOX READ DONE - 1 0 READ DONE
{98} LDO MBOX WRITE DONE - 1 0 WRITE DONE
{99} LAO ERROR STATUS - - 1 0 - -
FLN Detailed Point Descriptions
Point Description
Drive
Parameter
1 CTRL ADDRESS The FLN address of the drive. It can be set by FLN and by
the panel.
5302
2 APPLICATION The Application ID for FLN on the ACH550. This ID is
assigned by Siemens for each unique application. It
correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to ACH550 is 2734.
3 FREQ OUTPUT The output frequency applied to the motor, in Hertz. 0103
4 PCT OUTPUT The ratio of output frequency or speed to the corresponding
maximum rating, depending on control mode.
For scalar mode, it is the ratio of Output Frequency
(parameter 0103) to Maximum Frequency (parameter
2008).
For speed mode, it is the ratio Speed (parameter 0102) to
Maximum Speed (2002).
None. This
ratio is
calculated
by the FLN
application.
5 SPEED The calculated speed of the motor, in RPM. 0102
6 CURRENT The measured output current. 0104
7 TORQUE The calculated output torque of the motor as a percentage of
nominal torque.
0105
8 POWER The measured output power in KW. The FLN point definition
also supports horsepower by selecting English units.
0106
9 DRIVE TEMP The measured heatsink temperature, in
° C. The FLN point
definition also supports
° F by selecting English units.
0110
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope Intercept
On Text Off Text
# Type (SI Units)

Table of Contents