ACH550-UH User’s Manual 1-221
Embedded fieldbus
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets { } may be unbundled at the field panel.
Detailed point descriptions
{91} LAI PREV FAULT 1 - - 1 0 - -
{92} LAI PREV FAULT 2 - - 1 0 - -
{93} LDI OK.FAULT OK - 1 0 FAULT OK
{94} LDO RESET FAULT NO - 1 0 RESET NO
{95} LAO MBOX PARAM - - 1 0 - -
{96} LAO MBOX DATA - - 1 0 - -
{97} LDO MBOX READ DONE - 1 0 READ DONE
{98} LDO MBOX WRITE DONE - 1 0 WRITE DONE
{99} LAO ERROR STATUS - - 1 0 - -
FLN Detailed Point Descriptions
Point Description
Drive
Parameter
1 CTRL ADDRESS The FLN address of the drive. It can be set by FLN and by
the panel.
5302
2 APPLICATION The Application ID for FLN on the ACH550. This ID is
assigned by Siemens for each unique application. It
correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to ACH550 is 2734.
3 FREQ OUTPUT The output frequency applied to the motor, in Hertz. 0103
4 PCT OUTPUT The ratio of output frequency or speed to the corresponding
maximum rating, depending on control mode.
• For scalar mode, it is the ratio of Output Frequency
(parameter 0103) to Maximum Frequency (parameter
2008).
• For speed mode, it is the ratio Speed (parameter 0102) to
Maximum Speed (2002).
None. This
ratio is
calculated
by the FLN
application.
5 SPEED The calculated speed of the motor, in RPM. 0102
6 CURRENT The measured output current. 0104
7 TORQUE The calculated output torque of the motor as a percentage of
nominal torque.
0105
8 POWER The measured output power in KW. The FLN point definition
also supports horsepower by selecting English units.
0106
9 DRIVE TEMP The measured heatsink temperature, in
° C. The FLN point
definition also supports
° F by selecting English units.
0110
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope Intercept
On Text Off Text
# Type (SI Units)