1-222 ACH550-UH User’s Manual
Embedded fieldbus
10 DRIVE KWH The drive's cumulative power consumption in kilowatt-hours.
This value may be reset by commanding FLN point 49,
RESET KWH.
0115
11 DRIVE MWH The drive's cumulative power consumption in megawatt
hours. This value cannot be reset.
0141
12 RUN TIME The drive's cumulative run time in hours. This value may be
reset by commanding FLN point 48, RESET RUN TIME.
0114
13 DC BUS VOLT The DC bus voltage level of the drive. 0107
14 OUTPUT VOLT The AC output voltage applied to the motor. 0109
15 PRC PID FBCK The Process PID feedback signal. 0130
16 PRC PID DEV The deviation of the Process PID output signal from its
setpoint.
0132
17 MOTOR TEMP The measured motor temperature as set up in Group 35. 0145
18 ROTATION CNT The motor's cumulative revolution count, in mega-
revolutions.
0142
19 N/A
20 OVRD TIME 1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
21 FWD.REV ACT Indicates the rotational direction of the motor, regardless of
control source (1 = REV, 0 = FWD).
22 FWD.REV CMD Commanded by FLN to change the rotational direction of the
drive.
• Parameter 1001 must be set to COMM for FLN to control
the direction of the motor by EXT1.
• Parameter 1002 must be set to COMM for FLN to control
the direction of the motor by EXT2.
23 RUN.STOP ACT Indicates the drive's run status, regardless of control source
(1 = RUN, 0 = STOP).
24 RUN.STOP CMD Commanded by FLN to start the drive.
• Parameter 1001 must be set to COMM for FLN to control
the run state of the drive by EXT1.
• Parameter 1002 must be set to COMM for FLN to have
this control.
25 EXT1.2 ACT Indicates whether External 1 or External 2 is the active
control source (1 = EXT2, 0 = EXT1).
26 EXT1.2 CMD Commanded by FLN to select External 1 or External 2 as the
active control source (1 = EXT2, 0 = EXT1).
Parameter 1102 must be set to COMM for FLN to have this
control.
27 DRIVE READY Indicates the drive is ready to accept a run command
(1 = READY, 0 = NOTRDY).
28 AT SETPOINT Indicates the drive has reached its commanded setpoint
(1 = YES, 0 = NO)
29 DAY.NIGHT 1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None
FLN Detailed Point Descriptions
Point Description
Drive
Parameter