ACH550 E-Clipse Bypass User’s Manual 2-69
Parameters
Group 16: System Control
Group 16: System Control
Code Name Resolution Range Default Description
1601 START/STOP 1 0 = NOT SEL
1 = DI1
2 = COMM
DI 1
(1)
Selects source for system start
command.
1602 RUN
ENABLE
10 = NOT SEL
1 = DI2
2 = COMM
NOT SEL
(0)
Selects source for run enable
command.
1603 START EN 1 1 0 = NOT SEL
1 = DI3
2 = COMM
DI 3
(1)
Selects source for start enable 1
command.
1604 START EN 2 1 0 = NOT SEL
1 = DI4
2 = COMM
NOT SEL
(0)
Selects source for start enable 2
command.
1605 START EN 3 1 0 = NOT SEL
1 = DI5
2 = COMM
NOT SEL
(0)
Selects source for start enable 3
command.
1606 START EN 4 1 0 = NOT SEL
1 = DI2
2 = COMM
NOT SEL
(0)
Selects source for start enable 4
command.
1607 RESET SRC 1 0 = NOT SEL
1 = DI4
2 = COMM
NOT SEL
(0)
Selects source for fault reset
command (rising edge).
1608 AUTO XFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Enabled allows auto transfer to
bypass on all drive faults except
the conditional faults which
require an additional enable.
NOT SEL prevents auto transfer
to bypass for all drive faults
including the conditional faults.
1609 OC
TRANSFR
10 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive over current causes auto
transfer. Requires global auto
transfer enable also.
1610 OV
TRANSFR
10 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive over voltage causes auto
transfer. Requires global auto
transfer enable also.
1611 UV
TRANSFR
10 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive under voltage causes auto
transfer. Requires global auto
transfer enable also.
1612 AI TRANSFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive AI loss causes auto
transfer. Requires global auto
transfer enable also.
1613 BP DISABLE 1 0 = NOT SEL
1 = DISABLE
NOT SEL
(0)
Disables bypass mode.
1614 BP RUN DLY 1 sec 0 - 300 secs 0s Bypass contactor pick-up delay
when starting bypass or
transferring from Drive mode.