2-70 ACH550 E-Clipse Bypass User’s Manual
Parameters
1615 SAVE
PARAM
10 = DONE
1 = SAVE
0 Save User Settings (SaveImm +
SavePwrd).
1616 DISP ALRMS 1 0 = DISABLE
1 = ENABLE
ENABLE
(1)
Enables alarms to be displayed:
INP PHASE A LOSS,
INP PHASE B LOSS,
INP PHASE C LOSS,
MTR OVERLOAD,
BYPASS DISABLED,
DRIVE SETUP,
PCB TEMP
DRIVE LINK ERROR
DRIVE FAULTED
1617 DRIVE TEST 1 0 = DISABLE
1 = ENABLE
DISABLE
(0)
Enables drive test mode. Drive
contactor is opened.
1618 PASS CODE 1 0 - 65535 0 Enter correct password to here in
order to change value of the PAR
LOCK. Default password value is
"123".
1619 PAR LOCK 1 0 = LOCKED
1 = OPEN
OPEN
(1)
When switched to "LOCKED"
prevents parameter changes
from panel. Does not affect to
Field Bus writes, expect
changing the lock value itself:
correct password must always be
set first, even in case of Field
Bus.
1620 RUN EN TXT 1 0 = RUN ENABLE
1 = DAMPER END SWTCH
2 = VALVE OPENING
3 = PRE-LUBE CYCLE
RUN
ENABLE
(0)
Alternative text choices for alarm
4006.
1621 ST EN1 TXT 1 0 = START ENABLE 1
1 = VIBRATION SWITCH
2 = FIRESTAT
3 = FREEZESTAT
4 = OVERPRESSURE
5 = VIBRATION TRIP
6 = SMOKE ALARM
7 = SAFETY OPEN
8 = LOW SUCTION
START
ENABLE
1
(0)
Alternative text choices for alarm
4021.
1622 ST EN2 TXT 1 0 = START ENABLE 2
...
START
ENABLE
2
(0)
Alternative text choices for alarm
4022.
See parameter 1621 for range.
1623 ST EN3 TXT 1 0 = START ENABLE 3
...
START
ENABLE
3
(0)
Alternative text choices for alarm
4023.
See parameter 1621 for range.