2-72 ACH550 E-Clipse Bypass User’s Manual
Parameters
1630 START REV 0 = NOT SEL
1 = DI2
NOT SEL
(0)
Selects source for drive start
reverse command
Reverse request can only be
selected for DI2 on the Eclipse
Drive Param 1003 (Direction)
needs to be set for REQUEST.
Drive Param 1201 (Const
Speed Select) needs to be set
for DI3.
Drive Param 1202 (Const
Speed 1) needs to be set for
reverse speed required.
When Eclipse input DI2 is
energized the bypass sets
drive reverse run request over
comm’s.
The same signal input for
bypass DI2 goes to Drive DI3
and sets constant speed.
The Reverse request has
priority over normal Run input,
this means that if both are
present the motor will run
reverse at constant speed.
1631 DRV/BYPASS 1 0 = KEYPAD
1 = DI5
KEYPAD
(0)
Selects source for drive/bypass
mode command.
(0) Keypad – The drive/bypass
mode selection is made from
the bypass keypad
(DRIVEBYPASS select
keys).
(1) DI5 – The drive/bypass
mode selection from the
bypass keypad is disabled
and selection is made from
the digital input. When DI5 is
energized the system is set
to bypass mode.
Group 16: System Control
Code Name Resolution Range Default Description
Drve
ByPass
DI3
DComm
DComm
DI2
+24V
Rev Request