2-72 ACH550 E-Clipse Bypass User’s Manual
Parameters
1630 START REV 0 = NOT SEL
1 = DI2
NOT SEL
(0)
Selects source for drive start
reverse command
• Reverse request can only be
selected for DI2 on the Eclipse
• Drive Param 1003 (Direction)
needs to be set for REQUEST.
• Drive Param 1201 (Const
Speed Select) needs to be set
for DI3.
• Drive Param 1202 (Const
Speed 1) needs to be set for
reverse speed required.
• When Eclipse input DI2 is
energized the bypass sets
drive reverse run request over
comm’s.
• The same signal input for
bypass DI2 goes to Drive DI3
and sets constant speed.
• The Reverse request has
priority over normal Run input,
this means that if both are
present the motor will run
reverse at constant speed.
1631 DRV/BYPASS 1 0 = KEYPAD
1 = DI5
KEYPAD
(0)
Selects source for drive/bypass
mode command.
(0) Keypad – The drive/bypass
mode selection is made from
the bypass keypad
(DRIVEBYPASS select
keys).
(1) DI5 – The drive/bypass
mode selection from the
bypass keypad is disabled
and selection is made from
the digital input. When DI5 is
energized the system is set
to bypass mode.
Group 16: System Control
Code Name Resolution Range Default Description
Drve
ByPass
DI3
DComm
DComm
DI2
+24V
Rev Request