ACH550 E-Clipse Bypass User’s Manual 2-91
Embedded fieldbus
5005 EFB CTRL PROFILE
Selects the communication
profile used by the EFB
protocol.
0 =
ABB DRV LIM
Operation of Control/
Status Words conform to
limited ABB Drives
Profile, as used in
ACH400/550.
1 =
DCU PROFILE
Operation of Control/
Status Words conform to
32-bit DCU Profile.
2 =
ABB DRV FULL
Operation of Control/
Status Words conform to
ABB Bypass Profile, as
used in ACS600/800.
(Read Only Copy, edit in 5305)
5010 BP PAR10
Sets the response
turnaround time in
milliseconds.
(Read Only Copy, edit in 5310)
5011 BP PAR11 Not used for Comm setup. This parameter,
together with
parameter 5017, BP
PAR 17, sets BACnet
Device Object Instance
IDs:
For the range 1 to
65,535: This
parameter sets the
ID directly (5017
must be 0). For
example, the
following values set
the ID to 49134:
5011 = 49134 and
5017 = 0.
For IDs > 65,335:
The ID equals
5011’s value plus
10,000 times 5017’s
value. For example,
the following values
set the ID to 71234:
5011 = 1234 and
5017 = 7.
Bypass
Parameter
Description
EFB Protocol Reference
Modbus N2 FLN BACnet