ACH550 E-Clipse Bypass User’s Manual 2-91
Embedded fieldbus
5005 EFB CTRL PROFILE
Selects the communication 
profile used by the EFB 
protocol.
0 = 
ABB DRV LIM – 
Operation of Control/
Status Words conform to 
limited ABB Drives 
Profile, as used in 
ACH400/550.
1 = 
DCU PROFILE – 
Operation of Control/
Status Words conform to 
32-bit DCU Profile.
2 = 
ABB DRV FULL – 
Operation of Control/
Status Words conform to  
ABB Bypass Profile, as 
used in ACS600/800.
(Read Only Copy, edit in 5305)
5010 BP PAR10
Sets the response 
turnaround time in 
milliseconds.
(Read Only Copy, edit in 5310)
5011 BP PAR11 Not used for Comm setup. This parameter, 
together with 
parameter 5017, BP 
PAR 17, sets BACnet 
Device Object Instance 
IDs:
• For the range 1 to 
65,535: This 
parameter sets the 
ID directly (5017 
must be 0). For 
example, the 
following values set 
the ID to 49134: 
5011 = 49134 and 
5017 = 0.
• For IDs > 65,335: 
The ID equals 
5011’s value plus 
10,000 times 5017’s 
value. For example, 
the following values 
set the ID to 71234: 
5011 = 1234 and 
5017 = 7.
Bypass 
Parameter
Description
EFB Protocol Reference
Modbus N2 FLN BACnet