2-118 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
CSBO "BO11",Y,Y,"CMD_RO_5","OFF","ON"
CSBO "BO12",Y,Y,"CMD_RO_6","OFF","ON"
CSBO "BO13",Y,Y,"RST_RTIM","OFF","RESET"
CSBO "BO14",Y,Y,"RST_KWH","OFF","RESET"
CSBO "BO15",Y,Y,"PID_SEL","SET1","SET2"
CSBO "BO16",Y,Y,"N2_LOC_C","AUTO","N2"
CSBO "BO17",Y,Y,"N2_LOC_R","EUTO","N2"
CSBO "BO18",Y,Y,"SAV_PRMS","OFF","SAVE"
CSBO "BO19",Y,Y,"READ_MB","NO","READ"
CSBO "BO20",Y,Y,"WRITE_MB","NO","WRITE"
Bypass overview
The ABB E-Clipse bypass does not support N2 Fieldbus communication “internal
values”.
All of the Binary I/O objects are listed below.
Binary Input – The binary input objects support the following features:
• Binary Input actual value
• Normal / Alarm state specification
• Alarm Enabled
• Change of State (COS) enabled
• Override value is received, but there is no action taken.
Binary Output – The binary output objects support the following features:
• Binary Output value
• Override value is used to change the Binary Output value. It is not possible to
return to the previous value by removing the override. The override feature is
used only to change the value.
N2 analog input objects – bypass
The following table lists the N2 Analog Input objects defined for the ABB E-Clipse
bypass.
N2 Analog Inputs:
Number Object
Bypass
Parameter
Scale
Factor
Units Range
AI1 CURRENT 0101 10 A 0…9999
AI2 LAST FAULT 0401 1 fault code
AI3 ALARM WORD 1 0308 1 Alarm mask
(see bypass
manual
description of
parameter
0308)