2-142 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
Point database – bypass
The following table lists the point database for FLN / ABB E-Clipse bypass
(Application 2737).
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope Intercept
On Text Off Text
# Type (SI Units)
01 LAO CTLR ADDRESS 2 - 1 0 - -
02 LAO APPLICATION 2737 - 1 0 - -
05 LAI INPUT VOLT 0 V 1 0 - -
{06} LAI CURRENT 0 A 0.1 0 - -
{07} LAI SYS
UNDRLOAD
NO - 1 0 [YES] [NO]
09 LAI PCB TEMP 77 (25) °F (°C) 0.18
(0.1)
33 (0) - -
10 LAI KW HOURS 0 KWH 1 0 - -
12 LAI RUN TIME 0 HRS 1 0 - -
13 LAI A.B. VOLT 0 V 1 0 - -
14 LAI B.C. VOLT 0 V 1 0 - -
15 LAI C.A. VOLT 0 V 1 0 - -
20 LAO OVRD TIME 1 HRS 1 0 - -
{23} LDI MTR RUNNING STOP - 1 0 [RUN] [STOP]
{24} LDO RUN.STOP CMD STOP - 1 0 [RUN] [STOP]
{25} LDI OVERRIDE ACT OFF - 1 0 [ON] [OFF]
{26} LDO OVERRIDE CMD OFF - 1 0 [ON] [OFF]
{27} LDI SYSTEM
READY
NOT
READY
- 1 0 [READY] [NOT
READY]
{28} LDI SYS STARTED NO - 1 0 [YES] [NO]
{29} LDO DAY.NIGHT DAY - 1 0 [NIGHT] [DAY]
30 LAO BYP RUN DLY 0 SEC 1 0 - -
{31} LAI BYPASS MODE 0 - 1 0 - -
{32} LDI DRIVE.BYPASS DRIVE - 1 0 [BYPASS] [DRIVE]
{33} LDI BYP RUNNING NO - 1 0 [YES] [NO]
{34} LDI RUN ENA ACT DISABL - 1 0 [ENABLE] [DISABL]
{35} LDO RUN ENA CMD DISABL - 1 0 [ENABLE] [DISABL]
{36} LDI FLN LOC ACT AUTO - 1 0 [FLN] [AUTO]
{37} LDI FLN CTL SRC NO - 1 0 [YES] [NO]
{40} LDO RO 1
COMMAND
OFF - 1 0 [ON] [OFF]
{41} LDO RO 2
COMMAND
OFF - 1 0 [ON] [OFF]
{42} LDO RO 3
COMMAND
OFF - 1 0 [ON] [OFF]