ACH550 E-Clipse Bypass User’s Manual 2-145
Embedded fieldbus
{32} DRIVE.BYPASS This point indicates if the system is selected to operate the
motor from the drive or from the bypass.
{33} BYP RUNNING This point indicates the bypass’s run status. It differs from
the system running status in that it only applies to the
bypass’s status not the logical OR of the drive and bypass
status.
{34} RUN ENA ACT This point indicates the status of the system Run Enable
command, regardless of its source (1 = ENABLE, 0 =
DISABL).
{35} RUN ENA CMD This point is commanded by FLN to assert the system Run
Enable command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1602 must be set to COMM for FLN to have this
control.
{36} FLN LOC ACT This point indicates if the bypass has been placed in “FLN
LOCAL” mode by commanding point 68 (FLN LOCAL).
Commanding this point to FLN (1) “steals” control from its
normal source and places it in FLN control. Note that the
HAND mode of the panel has priority over FLN local control.
{37} FLN CTL SRC This point indicates if FLN is a source for control inputs (1 =
YES, 0 = NO). Note that this status point is true if any of the
following control inputs are from FLN: Run/ Stop, Run
Enable, Start Enable 1, Start Enable 2, Start Enable 3 or
Start Enable 4.
{40} RO 1
COMMAND
This point controls the output state of bypass Relay 1.
Bypass parameter 1401 must be set to COMM for FLN to
have this control (1 = ON, 0 = OFF).
0107, bit 0
{41} RO 2
COMMAND
This point controls the output state of bypass Relay 2.
Bypass parameter 1401 must be set to COMM for FLN to
have this control (1 = ON, 0 = OFF).
0107, bit 1
{42} RO 3
COMMAND
This point controls the output state of bypass Relay 3.
Bypass parameter 1401 must be set to COMM for FLN to
have this control (1 = ON, 0 = OFF).
0107, bit 2
{43} RO 4
COMMAND
This point controls the output state of bypass Relay 4.
Bypass parameter 1401 must be set to COMM for FLN to
have this control (1 = ON, 0 = OFF).
0107, bit 3
{44} RO 5
COMMAND
This point controls the output state of bypass Relay 5.
Bypass parameter 1401 must be set to COMM for FLN to
have this control (1 = ON, 0 = OFF).
0107, bit 4
{48} RESET RUN
TIME
Run Time reset 0108
{49} RESET KW
HOURS
Kilowatt hours reset 0106
{50} START ENA 1 This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1603 must be set to COMM for FLN to have this
control.
{51} START ENA 2 This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1604 must be set to COMM for FLN to have this
control.
FLN Detailed Point Descriptions
Point Description
Drive
Parameter