2-146 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
{52} START ENA 3 This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1605 must be set to COMM for FLN to have this
control.
{53} START ENA 4 This point is commanded by FLN to assert the system Start
Enable 1 command (1 = ENABLE, 0 = DISABL). Bypass
parameter 1606 must be set to COMM for FLN to have this
control.
{59} PAR LOCK When switched to locked prevents parameter changes from
the panel.
1619
{68} FLN LOC CTL Commands the bypass into FLN Local Control. In this
mode, FLN takes the bypass control from the normal
source. However, the panel’s HAND mode still has priority.
{70} DI 1 ACTUAL This point indicates the status of bypass Digital Input 1
(1 = ON, 0 = OFF).
0103, bit 5
{71} DI 2 ACTUAL This point indicates the status of bypass Digital Input 2
(1 = ON, 0 = OFF).
0103, bit 4
{72} DI 3 ACTUAL This point indicates the status of bypass Digital Input 3
(1 = ON, 0 = OFF).
0103, bit 3
{73} DI 4 ACTUAL This point indicates the status of bypass Digital Input 4
(1 = ON, 0 = OFF).
0103, bit 2
{74} DI 5 ACTUAL This point indicates the status of bypass Digital Input 5
(1 = ON, 0 = OFF).
0103, bit 1
{75} DI 6 ACTUAL This point indicates the status of bypass Digital Input 6
(1 = ON, 0 = OFF).
0103, bit 0
{76} RO 1 ACTUAL This point indicates the status of bypass Relay Output 1
(1 = ON, 0 = OFF).
0104, bit 4
{77} RO 2 ACTUAL This point indicates the status of bypass Relay Output 2
(1 = ON, 0 = OFF).
0104, bit 3
{78} RO 3 ACTUAL This point indicates the status of bypass Relay Output 3
(1 = ON, 0 = OFF).
0104, bit 2
{79} RO 4 ACTUAL This point indicates the status of bypass Relay Output 4
(1 = ON, 0 = OFF).
0104, bit 1
{80} RO 5 ACTUAL This point indicates the status of bypass Relay Output 5
(1 = ON, 0 = OFF).
0104, bit 0
86 BYPASS ALARM This point indicates the current alarm state of the bypass
(1 = ALARM, 0 = OK).
88 ALARM WORD1 This point is a bit-field indicating active alarms in the
bypass.
0308
89 ALARM WORD2 This point is a bit-field indicating active alarms in the
bypass.
0309
90 LAST FAULT This point is first in the bypass’s fault log and indicates the
most recent fault declared.
0401
93 OK.FAULT BYP This point indicates the current fault state of the bypass
(1 = FAULT, 0 = OK).