ACH550 E-Clipse Bypass User’s Manual 2-149
Embedded fieldbus
5304 EFB PARITY 0 This parameter sets the BACnet MS/TP character
format as follows:
0 = 8N1
1 = 8N2
2 = 8E1
3 = 8O1.
5305 EFB CTRL PROFILE - This parameter indicates the active control profile.
This parameter has no affect on BACnet behavior.
5306 EFB OK MESSAGES - This parameter indicates the number of valid
application messages received at this drive. This
count does not include MS/TP token passing and
polling messages. (For such messages, see
5316).
5307 EFB CRC ERRORS - This parameter indicates the number of CRC
errors detected, in either the header or data CRCs.
5308 EFB UART ERRORS - This parameter indicates the number of UART-
related errors (framing, parity) detected.
5309 EFB STATUS - This parameter indicates the internal status of the
BACnet channel as follows:
IDLE – BACnet channel is configured but not
receiving messages.
TIMEOUT – Time between valid messages has
exceeded the interval set by parameter 3019.
OFFLINE – BACnet channel is receiving
messages NOT addressed to this drive.
ONLINE – BACnet channel is receiving
messages addressed to this drive.
RESET – BACnet channel is in reset.
LISTEN ONLY – BACnet channel is in listen-
only mode.
5310 EFB PAR 10 5 This parameter sets the BACnet MS/TP response
turn-around time, in milliseconds.
5311 EFB PAR 11 0 This parameter, together with parameter 5317,
EFB PAR 17, sets BACnet object instance IDs:
For the range 1 to 65,535: This parameter sets
the ID directly (5317 must be 0). For example,
the following values set the ID to 49134: 5311 =
49134 and 5317 = 0.
For IDs > 65,535: The ID equales 5311’s value
plus 10,000 times 5317’s value. For example,
the following values set the ID to 71234: 5311 =
1234 and 5317 =7/
5312 EFB PAR 12 1 This parameter sets the BACnet Device Object
Max Info Frames property.
5313 EFB PAR 13 127 This parameter sets the BACnet Device Object
Max Master property.
5314 EFB PAR 14 0 N/A Not supported with BACnet Protocol Version
0506 and higher
5315 EFB PAR 15 N/A Not supported with BACnet Protocol Version
0506 and higher
Parameter
Default
Value
BACnet-specific Description