2-150 ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
Note: The system will function as a master with MAC IDs in the range of 1-127. With
MAC ID settings of 128-254, the drive is in slave only mode.
Changes made to drive parameter Group 53, EFB Protocol, do not take affect until
you perform one of the following:
Cycle the bypass power OFF and ON, or
Set bypass parameter 5302 to 0, and then back to a unique MAC ID, or
Use the ReinitializeDevice service.
Quick-start sequence - drive communications
The following steps summarize the process for enabling and configuring BACnet on
the ABB E-Clipse Bypass:
1. Enable BACnet protocol: Set bypass parameter 9802,
COMM PROTOCOL SEL BACNET
(5).
To confirm this selection, read bypass parameter 5301,
EFB PROTOCOL ID. It
should read x5xx (where “x” is any value).
2. Place the BACnet channel in “reset”: Set bypass parameter 5302,
EFB STATION ID = 0.
This setting holds the BACnet communication channel in reset while remaining
settings are completed.
3. Define the MS/TP baud rate.
Set bypass parameter 5303,
EFB BAUD RATE = appropriate value
4. Define the Device Object instance.
To define a specific device object instance value, use bypass parameters 5311
and 5317 (object instance values must be unique and in the range 1 to
4,194,303).
To use the bypass’ MS/TP MAC ID as the device object instance value, set
bypass parameter 5311 and 5317 = 0.
BACnet requires a unique Device Object ID for each device on the BACnet
network.
5316 EFB PAR 16 0 This parameter indicates the count of MS/TP
tokens passed to this drive.
5317 EFB PAR 17 0 This parameter works with paramter 5311 to set
BACnet instance IDs. See parameter 5311.
5318 …
5320
EFB PAR 18…20 N/A - Not supported with BACnet protocol.