ACH550 E-Clipse Bypass User’s Manual 2-151
Embedded fieldbus
5. Define a unique MS/TP MAC ID. Set bypass parameter 5302, EFB STATION ID =
appropriate value.
• Once this parameter is set to a non-zero value, current BACnet settings are
“latched” and used for communication until the channel is reset.
• In order to participate in MS/TP token passing, the MAC ID used must be within
the limits defined by other masters’ “Max Master” property.
6. Confirm proper BACnet communication.
• When BACnet communication is operating properly, bypass parameter 5316,
EFB PAR 16 (the MS/TP token counter), should be continually increasing.
• Bypass parameter 5306,
UART ERRORS, should be stable.
7. Configure the Device Object Name.
• BACnet requires a unique name for each device on the BACnet network. Write
the Object Name of the Device Object of the drive to a unique text string using the
operator workstation or software tool capable of writing BACnet properties. The
Object Name cannot be modified with the ABB display panel and only the Device
object name is writable in this product. We do not support writing of Device
Description.