ACH550-UH User’s Manual 1-75
Parameters
3615 STOP TIME 4 00:00:00…23:59:58 2 s 12:00:00 AM
3616
START DAY 4 1…7 1 1 (MONDAY)
3617 STOP DAY 4 1…7 1 1 (MONDAY)
3622
BOOSTER SEL -6…6 1 0 (NOT SEL)
3623
BOOSTER TIME 00:00:00…23:59:58 2 s 00:00:00
3626
…
3629
TIMED FUNC 1…4 SRC 0…31 1 0 (NOT SEL)
Group 37: USER LOAD CURVE
3701 USER LOAD C MODE 0…3 1 0 (NOT SEL)
3702
USER LOAD C FUNC 1, 2 1 1 (FAULT)
3703
USER LOAD C TIME 10…400 s 1 s 20 s
3704 LOAD FREQ 1 0…500 Hz 1 Hz 5 Hz
3705
LOAD TORQ LOW 1 0…600% 1% 10%
3706
LOAD TORQ HIGH 1 0…600% 1% 300%
3707 LOAD FREQ 2 0…500Hz 1Hz 25Hz
3708
LOAD TORQ LOW 2 0…600% 1% 15%
3709
LOAD TORQ HIGH 2 0…600% 1% 300%
3710 LOAD FREQ 3 0…500Hz 1Hz 43Hz
3711
LOAD TORQ LOW 3 0…600% 1% 25%
3712
LOAD TORQ HIGH 3 0…600% 1% 300%
3713 LOAD FREQ 4 0…500Hz 1Hz 50Hz
3714
LOAD TORQ LOW 4 0…600% 1% 30%
3715
LOAD TORQ HIGH 4 0…600% 1% 300%
3716 LOAD FREQ 5 0…500 Hz 1 Hz 500 Hz
3717
LOAD TORQ LOW 5 0…600% 1% 30%
3718
LOAD TORQ HIGH 5 0…600% 1% 300%
Group 40: PROCESS PID SET 1
4001
GAIN 0.1…100.0 0.1 2.5
4002
INTEGRATION TIME 0.0…3600.0 s 0.1 s 3.0 s
4003
DERIVATION TIME 0.0…10.0 s 0.1 s 0.0 s
4004
PID DERIV FILTER 0.0…10.0 s 0.1 s 1.0 s
4005
ERROR VALUE INV 0, 1 1 0 (NO)
4006
UNITS 0…127 1 4 (%)
4007
UNIT SCALE 0…4 1 1
4008 0%
VALUE Depends on Units and Scale - 0.0%
4009 100%
VALUE Depends on Units and Scale - 100.0%
4010
SET POINT SEL 0…2, 8…17, 19…20 1 0 (KEYPAD)
4011
INTERNAL SETPNT Depends on Units and Scale - 40.0%
4012
SETPOINT MIN -500.0…500.0% 0.1% 0.0%
4013
SETPOINT MAX -500.0…500.0% 0.1% 100.0%
4014 FBK SEL 1…13 1 1 (ACT1)
4015
FBK MULTIPLIER -32.768…32.767 0.001 0.000 (NOT SEL)
4016
ACT1 INPUT 1…7 1 2 (AI2)
4017
ACT2 INPUT 1…7 1 2 (AI2)
Code Name Range Resolution Default User S