1-76 ACH550-UH User’s Manual
Parameters
4018 ACT1 MINIMUM -1000…1000% 1% 0%
4019
ACT1 MAXIMUM -1000…1000% 1% 100%
4020 ACT2 MINIMUM -1000…1000% 1% 0%
4021
ACT2 MAXIMUM -1000…1000% 1% 100%
4022
SLEEP SELECTION -6…7 1 0 (NOT SEL)
4023 PID SLEEP LEVEL 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
4024
PID SLEEP DELAY 0.0…3600.0 s 0.1 s 60.0 s
4025 WAKE-UP DEV Depends on Units and Scale - 0.0%
4026
WAKE-UP DELAY 0.00…60.00 s 0.01 s 0.50 s
4027
PID 1 PARAM sET -6…14 1 0 (SET 1)
Group 41: PROCESS PID SET 2
4101
GAIN 0.1…100.0 0.1 2.5
4102
INTEGRATION TIME 0.0…3600.0 s 0.1 s 3.0 s
4103
DERIVATION TIME 0.0…10.0 s 0.1 s 0.0 s
4104
PID DERIV FILTER 0.0…10.0 s 0.1 s 1.0 s
4105
ERROR VALUE INV 0, 1 1 0 (NO)
4106 UNITS 0…127 1 4 (%)
4107
UNIT SCALE 0…4 1 1
4108 0%
VALUE Depends on Units and Scale - 0.0%
4109 100% VALUE Depends on Units and Scale - 100.0%
4110
SET POINT SEL 0…2, 8…17, 19…20 1 0 (KEYPAD)
4111
INTERNAL SETPNT Depends on Units and Scale - 40.0%
4112 SETPOINT MIN -500.0…500.0% 0.1% 0.0%
4113
SETPOINT MAX -500.0…500.0% 0.1% 100.0%
4114
FBK SEL 1…13 1 1 (ACT1)
4115 FBK MULTIPLIER -32.768…32.767 0.001 0.000 (NOT SEL)
4116
ACT1 INPUT 1…7 1 2 (AI2)
4117
ACT2 INPUT 1…7 1 2 (AI2)
4118 ACT1 MINIMUM -1000…1000% 1% 0%
4119
ACT1 MAXIMUM -1000…1000% 1% 100%
4120
ACT2 MINIMUM -1000…1000% 1% 0%
4121
ACT2 MAXIMUM -1000…1000% 1% 100%
4122
SLEEP SELECTION -6…7 1 0 (NOT SEL)
4123
PID SLEEP LEVEL 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
4124
PID SLEEP DELAY 0.0…3600.0 s 0.1 s 60.0 s
4125
WAKE-UP DEV Depends on Units and Scale - 0.0%
4126
WAKE-UP DELAY 0.00…60.00 s 0.01 s 0.50 s
Group 42: EXT / TRIM PID
4201
GAIN 0.1…100.0 0.1 1.0
4202
INTEGRATION TIME 0.0…3600.0 s 0.1 s 60.0 s
4203
DERIVATION TIME 0.0…10.0 s 0.1 s 0.0 s
4204
PID DERIV FILTER 0.0…10.0 s 0.1 s 1.0 s
4205
ERROR VALUE INV 0, 1 1 0 (NO)
4206
UNITS 0…127 1 4 (%)
4207
UNIT SCALE 0…4 1 1
Code Name Range Resolution Default User S