ACH550-UH User’s Manual 1-79
Parameters
6423 AL1RANGE90TO 0.0…100.0% 0.1% -
6424
AL2RANGE0TO10 0.0…100.0% 0.1% -
6425 AL2RANGE10TO20 0.0…100.0% 0.1% -
6426
AL2RANGE20TO30 0.0…100.0% 0.1% -
6427
AL2RANGE30TO40 0.0…100.0% 0.1% -
6428 AL2RANGE40TO50 0.0…100.0% 0.1% -
6429
AL2RANGE50TO60 0.0…100.0% 0.1% -
6430 AL2RANGE60TO70 0.0…100.0% 0.1% -
6431
AL2RANGE70TO80 0.0…100.0% 0.1% -
6432
AL2RANGE80TO90 0.0…100.0% 0.1% -
6433 AL2RANGE90TO 0.0…100.0% 0.1% -
Group 81: PFA CONTROL
8103
REFERENCE STEP 1 0.0…100.0% 0.1% 0.0%
8104
REFERENCE STEP 2 0.0…100.0% 0.1% 0.0%
8105
REFERENCE STEP 3 0.0…100.0% 0.1% 0.0%
8109
START FREQ 1 0.0…500.0 Hz 0.1 Hz 60.0 Hz (US)
8110 START FREQ 2 0.0…500.0 Hz 0.1 Hz 60.0 Hz (US)
8111
START FREQ 3 0.0…500.0 Hz 0.1 Hz 60.0 Hz (US)
8112
LOW FREQ 1 0.0…500.0 Hz 0.1 Hz 30.0 Hz (US)
8113 LOW FREQ 2 0.0…500.0 Hz 0.1 Hz 30.0 Hz (US)
8114
LOW FREQ 3 0.0…500.0 Hz 0.1 Hz 30.0 Hz (US)
8115
AUX MOT START D 0.0…3600.0 s 0.1 s 5.0 s
8116 AUX MOT STOP D 0.0…3600.0 s 0.1 s 3.0 s
8117
NR OF AUX MOT 0…4 1 1
8118
AUTOCHNG INTERV -0.1336.0h 0.1h 0.0h (NOT SEL)
8119 AUTOCHNG LEVEL 0.0…100.0% 0.1% 50.0%
8120
INTERLOCKS 0…6 1 4 (DI4)
8121
REG BYPASS CTRL 0, 1 1 0 (NO)
8122 PFA START DELAY 0.00…10.00 s 0.01 s 0.50 s
8123
PFA ENABLE 0, 1 1 0 (NOT SEL)
8124
ACC IN AUX STOP 0.0…1800.0 s 0.1 s 0.0 s (NOT SEL)
8125
DEC IN AUX START 0.0…1800.0 s 0.1 s 0.0 s (NOT SEL)
8126
TMED AUTOCHNG 0…4 1 0 (NOT SEL)
8127
MOTORS 1…7 1 2
8128
AUX START ORDER 1, 2 1 1 (EVEN RUNTIME)
Group 98: OPTIONS
9802
COMM PROT SEL 0…5 1 0 (NOT SEL)
Code Name Range Resolution Default User S