ACH550-UH User’s Manual 1-85
Parameters
0144 DRIVE ON TIME LO 00:00:00…23:59:58 1 = 2 s -
The drive’s accumulated power-on time in 2 second ticks (30 ticks = 60 seconds).
Shown in format hh.mm.ss.
Cannot be reset.
0145 MOTOR TEMP Par. 3501 = 1…3: 1 -
-10…200 °C
Par. 3501 = 4: 0…5000 ohm
Par. 3501 = 5…6: 0…1
Motor temperature in degrees Celsius / PTC resistance in ohms.
Applies only if motor temperature sensor is set up.
See parameter 3501.
0150 CB TEMP -20.0…150.0 °C 1.0 °C -
Temperature of the drive control board in degrees Celsius.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 °C.
0153 MOT THERM STRESS 0.0…100.0% 0.1% -
Estimated rise of the motor temperature. Value equals to the estimated motor thermal stress as a percentage of the
motor temperature trip level.
0158 PID COMM VALUE 1 -32768…+32767 1 -
Data received from fieldbus for PID control (PID1 and PID2).
0159 PID COMM VALUE 2 -32768…+32767 1 -
Data received from fieldbus for PID control (PID1 and PID2).
0174 SAVED KWH 0.0…999.9 kWh 0.1 kWh -
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply. See the note
on page 1-162.
The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0.
Can be reset with parameter 4509
ENERGY RESET (resets all energy calculators at the same time).
•See Group 45: ENERGY SAVING.
0175 SAVED MWH 0…65535 MWh 1 MWh -
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply. See the note
on page 1-162.
The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
Can be reset with parameter 4509
ENERGY RESET (resets all energy calculators at the same time).
•See Group 45: ENERGY SAVING.
0176 SAVED AMOUNT 1 0.0…999.9 0.1 -
Energy saved in local currency (remainder when the total saved energy is divided by 1000). See the note on
page 1-162.
To find out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the
value of parameter 0176.
Example:
0176
SAVED AMOUNT 1 = 123.4
0177
SAVED AMOUNT 2 = 5
Total saved energy = 5 · 1000 + 123.4 = 5123.4 currency units.
The counter value is accumulated till it reaches 999.9 (the counter does not roll over).
Can be reset with parameter 4509
ENERGY RESET (resets all energy calculators at the same time).
Local energy price is set with parameter 4502
ENERGY PRICE.
•See Group 45: ENERGY SAVING.
Group 01: Operating Data
Code Description Range Resolution Default S