Loading...
12 EN – US quick installation guide
EN
US
DE
ES
FI
FR
FR
NL
PL
PT
RU
SV
TR
ZH
YY: 17, 18, 19, … for 2017, 2018, 2019,
WW: 01, 02, 03, … for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter module capacitor
reforming instructions (3BFE64059629 [English]), available on the Internet at
abb.com/drives/documents
.
Data
IEC ratings
UL (NEC) ratings
ACH580-31-
Cu cable
(AWG/kcmil)
UL fuse Losses
(W)
3-phase U
N
= 480 V
09A5-4 14 JJS-15 219
12A7-4 14 JJS-20 278
018A-4 14 JJS-25 321
026A-4 10 JJS-35 473
033A-4 8 JJS-40 625
039A-4 8 JJS-50 711
046A-4 6 JJS-60 807
062A-4 4 JJS-80 960
073A-4 2 JJS-90 1223
088A-4 1/0 JJS-110 1560
106A4 2/0 JJS-150 1678
145A-4 3/0 JJS-200 2237
169A-4 250 MCM JJS-225 2796
206A-4 300 MCM JJS-300 3356
3AXD00000586715
ACH580-31-
Cu cable
(AWG/kcmil)
UL fuse Losses
(W)
3-phase U
N
= 480 V
07A6-4 14 JJS-15 219
012A-4 14 JJS-20 278
014A-4 14 JJS-25 321
023A-4 10 JJS-35 473
027A-4 8 JJS-40 625
034A-4 8 JJS-50 711
044A-4 6 JJS-60 807
052A-4 4 JJS-80 960
065A-4 2 JJS-90 1223
077A-4 2 JJS-110 1560
096A-4 1/0 JJS-150 1678
124A-4 2/0 JJS-200 2237
156A-4 4/0 JJS-225 2796
180A-4 250 MCM JJS-300 3356
3AXD00000586715