Check if capacitors need to be reformed
Reform the capacitors if the drive has not been powered up (either in storage or
unused) for a year or more.
You can determine the manufacturing date from the serial number, which you find on
the type designation label attached to the drive. The serial number is of format
XYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
YY: 17, 18, 19, … for 2017, 2018, 2019,
WW: 01, 02, 03, … for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter modules with
electrolytic DC capacitors in the DC link capacitor reforming instructions
(3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents
.
Data
IEC ratings
Select the power cables
See Data on page 4.
Ensure cooling
See Data on page 4. No condensation or frost is allowed. The allowed operating
temperature range of the drive without derating is -15 to +40 °C.
ACH580-31-
Cable
Cu (mm
2
) aR fuse Losses
(W)
3-phase U
N
= 400 V
09A5-4 3×2.5+2.5 170M1561 226
12A7-4 3×2.5+2.5 170M1561 329
018A-4 3×2.5+2.5 170M1563 395
026A-4 3×6+6 170M1563 579
033A-4 3×10+10 170M1565 625
039A-4 3×10+10 170M1565 751
046A-4 3×16+16 170M1566 912
062A-4 3×25+16 170M1567 1088
073A-4 3×35+16 170M1568 1502
088A-4 3×50+25 170M1568 1904
106A-4 3×70+35 170M1569 1877
145A-4 3×95+50 170M1570 2963
169A-4 3×120+70 170M5809 3168
206A-4 3×150+70 170M5810 3990