142 ACH580 Installation, Operation and Maintenance Manual
ACH580-PCR/PDR
Power connection terminals
The following tables show maximum wire size and required tightening torque for
incoming power, grounding and motor terminals.
1)“PxR” represents both PCR and PDR.
208/230 Volt
Output
Ratings
Base
Drive
Frame
Size
Maximum Power Wiring Data
Type Code
1
AHP
Circuit
Breaker
UL
(NEMA)
Type 1
and 12
Circuit
Breaker
UL (NEMA)
Type 3R
Disconnect
Switch
UL (NEMA)
Type 1
and 12
Disconnect
Switch
UL (NEMA)
Type 3R
Motor
Terminals
Ground
Lugs
UL
(NEMA)
Type 1
and 12
Ground
Lugs
UL
(NEMA)
Type 3R
ACH580-PxR-04A6-2 4.6 1 R1
#10
62 in-lbs
#10
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#10
0.7 ft-lbs
#2
50 in-lbs
#2
50 in-lbs
ACH580-PxR-06A6-2 6.6 1.5 R1
ACH580-PxR-07A5-2 7.5 2 R1
ACH580-PxR-10A6-2 10.6 3 R1
ACH580-PxR-017A-2 16.7 5 R1
#6
62 in-lbs
#6
62 in-lbs
#6
55 in-lbs
#6
55 in-lbs
ACH580-PxR-024A-2 24.2 7.5 R2
#6
1.1 ft-lbs
ACH580-PxR-031A-2 30.8 10 R2
#4
62 in-lbs
#4
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
ACH580-PxR-046A-2 46.2 15 R3
#2
62 in-lbs
#2
62 in-lbs
#2
55 in-lbs
#2
55 in-lbs
#2
2.6 ft-lbs
ACH580-PxR-059A-2 59.4 20 R3
#1
62 in-lbs
#1
62 in-lbs
#1
55 in-lbs
#1
55 in-lbs
ACH580-PxR-075A-2 74.8 25 R4
#1/0
62 in-lbs
#1/0
62 in-lbs
#1/0
55 in-lbs
#1/0
55 in-lbs
#1
3.0 ft-lbs
ACH580-PxR-088A-2 88 30 R5
#2/0
124 in-lbs
Consult
Factory
#2/0
275 in-lbs
Consult
Factory
#2/0
4.1 ft-lbs
#1/0
50 in-lbs
Consult
Factory
ACH580-PxR-114A-2 114 40 R5
#1/0
124 in-lbs
#4/0
275 in-lbs
ACH580-PxR-143A-2 143 50 R6
#3/0
124 in-lbs
200 MCM
275 in-lbs
300 MCM
22.1 ft-lbs
ACH580-PxR-169A-2 169 60 R7
#4/0
124 in-lbs
500 MCM
29.5 ft-lbs
ACH580-PxR-211A-2 211 75 R7
2 X 500
MCM
274 in-lbs
2 X 500
MCM
274 in-lbs
ACH580-PxR-248A-2 248 100
2
R8
373
MCM
274 in-lbs
2 x 300
MCM
29.6 ft-lbs
1) “PxR” represents both PCR and PDR.
2) 100 HP @ 230V.