142 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
For the 1xxxx registers:
• Additional discrete inputs are added sequentially.
The system supports the following Modbus function codes for discrete inputs:
3xxxx Mapping – Modbus Inputs. The drive maps the following information to the
3xxxx Modbus addresses called Modbus input registers:
• Any user defined analog inputs.
The following table summarizes the input registers:
The ACH580 supports the following Modbus function codes for 3xxxx registers:
4xxxxx Register Mapping. The drive maps its parameters and other data to the
4xxxxx holding registers as follows:
• 400001…400099 map to drive control and actual values. These registers are
described in the table below.
• 400101…465535 map to drive parameters or bypass parameters. Register
addresses that do not correspond to drive parameters are invalid. If there is an
10027 STATUS WORD – Bit 26 Reserved REQ_CTL
10028 STATUS WORD – Bit 27 Reserved REQ_REF1
10029 STATUS WORD – Bit 28 Reserved REQ_REF2
10030 STATUS WORD – Bit 29 Reserved REQ_REF2EXT
10031 STATUS WORD – Bit 30 Reserved ACK_STARTINH
10032 STATUS WORD – Bit 31 Reserved ACK_OFF_ILCK
10033 DI1 DI1 DI1
10034 DI2 DI2 DI2
10035 DI3 DI3 DI3
10036 DI4 DI4 DI4
10037 DI5 DI5 DI5
10038 DI6 DI6 DI6
1) = Active low
Function Code Description
02 Read input status
Modbus
Reference
Internal
Location
(All Profiles)
Remarks
30001 AI1 This register shall report the level of Analog Input 1 (0…100%).
30002 AI2 This register shall report the level of Analog Input 2 (0…100%).
Function Code Description
04 Read 3xxxx input status
Modbus
Ref.
Internal Location
(All Profiles)
ABB DRV
BP Param
(5825 = 0 or 2)
DCU PROFILE
BP Param
(5825 = 1)