142 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
For the 1xxxx registers:
Additional discrete inputs are added sequentially.
The system supports the following Modbus function codes for discrete inputs:
3xxxx Mapping – Modbus Inputs. The drive maps the following information to the
3xxxx Modbus addresses called Modbus input registers:
Any user defined analog inputs.
The following table summarizes the input registers:
The ACH580 supports the following Modbus function codes for 3xxxx registers:
4xxxxx Register Mapping. The drive maps its parameters and other data to the
4xxxxx holding registers as follows:
400001…400099 map to drive control and actual values. These registers are
described in the table below.
400101…465535 map to drive parameters or bypass parameters. Register
addresses that do not correspond to drive parameters are invalid. If there is an
10027 STATUS WORD – Bit 26 Reserved REQ_CTL
10028 STATUS WORD – Bit 27 Reserved REQ_REF1
10029 STATUS WORD – Bit 28 Reserved REQ_REF2
10030 STATUS WORD – Bit 29 Reserved REQ_REF2EXT
10031 STATUS WORD – Bit 30 Reserved ACK_STARTINH
10032 STATUS WORD – Bit 31 Reserved ACK_OFF_ILCK
10033 DI1 DI1 DI1
10034 DI2 DI2 DI2
10035 DI3 DI3 DI3
10036 DI4 DI4 DI4
10037 DI5 DI5 DI5
10038 DI6 DI6 DI6
1) = Active low
Function Code Description
02 Read input status
Modbus
Reference
Internal
Location
(All Profiles)
Remarks
30001 AI1 This register shall report the level of Analog Input 1 (0…100%).
30002 AI2 This register shall report the level of Analog Input 2 (0…100%).
Function Code Description
04 Read 3xxxx input status
Modbus
Ref.
Internal Location
(All Profiles)
ABB DRV
BP Param
(5825 = 0 or 2)
DCU PROFILE
BP Param
(5825 = 1)