38 ACS 300 User’s Manual
Chapter 5 - Start-up
Checking the
Parameters
Use the parameter tables starting on page 47 to write down your
customised settings.
Start-up data
Before proceeding with the commissioning, check and complete
the following Page 1 and Page 4 parameters which define the
motor connected to the ACS 300 and mains supply (400 V series
only):
NOM RPM = Nominal motor speed
NOM FREQ = Nominal motor frequency
NOM VOLT = Nominal motor voltage
COS PHI = Cos phi of the motor
SUPPLY VOLT = Supply voltage (400 V series only)
Note! Supply voltage should be set before giving the nominal
voltage of the motor. See parameter NOM VOLT in chapter 7 on
page 54.