ACS 300 User’s Manual 47
Chapter 7 - Drive Parameters
Note! The factory setting for display language is English, refer to
Page 1 parameter LANGUAGE for display language selection.
Parameters marked with (0) can only be altered with the
ACS 300 stopped otherwise START IS ACTIVE message is
displayed. (L) indicates that the parameter can be altered in Local
control mode only.
Table 7-1Drive parameters and their factory settings.
Code Parameter Range Default
Cus
tomer
Page Description
PAGE 1 (*P2) Display only - - 51 Press
to change to
page 2
101 OUTPUT f Display only 51 Frequency to motor
102 REF FREQ/
LOC FREQ (L)
f
MIN
f
MAX
0 Hz 51 Frequency reference from
remote or control panel
103 SPEED Display only 51 Calculated motor speed
104 OUTPUT I Display only 52 Motor current
105 COPY Exit/Read/Write/
Set Factory Def.
Exit 52 Transfers all settings to and
from panel
106 MIN FREQ 0.0 – 200/500 Hz
1)
0.0 Hz 52 Reference input minimum
frequency
107 MAX FREQ 0.0 – 200/500 Hz
1)
50 Hz 52 Maximum output frequency
108 ACC 1 0.1 – 1800 s 3 s 52 Time for Ref Min f - Ref Max f
acceleration ramp
109 DEC 1 0.1 – 1800 s 3 s 52 Time for Ref Max f - Ref Min f
deceleration ramp
110 ACC 2 0.1 – 1800 s 3 s 52 Time for Ref Min f - Ref Max f
acceleration ramp