Safety Instructions
10 ACS 600 MultiDrive
* manufactured before 1992
Manufacturer
Motor Type Nominal Mains
Voltage
Requirement for
Motor
Insulation
System
ACS 600 du/dt Filter, ACS 600 Common Mode Filter and Insulated N-
bearing
P
N
< 100 kW
and
Frame Size < IEC 315
100 kW < P
N
< 350 kW
or
Frame Size >
IEC 315
P
N
> 350 kW
A
B
B
Random-
wound
M2_ and M3_
U
N
< 500 V Standard - + N + N + CMF
500 V < U
N
< 600 V Standard + du/dt + du/dt + du/dt + N + LCMF
or
Reinforced - + N + N + CMF
600 V < U
N
< 690 V Reinforced + du/dt + du/dt + du/dt + N + LCMF
Form-wound
HXR and AM_
380 V < U
N
< 690 V Standard n.a. + N + CMF + N + CMF
Old* form-
wound HX_
and modular
380 V < U
N
< 690 V Check from
the motor
manufacturer.
+ du/dt filter with voltages over 500 V + N + CMF
Random-
wound HXR
380 V < U
N
< 690 V Check from
the motor
manufacturer.
+ du/dt filter with voltages over 500 V + N + CMF
N
O
N
-
A
B
B
Random-
wound
U
N
< 420 V Standard:
Û
LL
= 1300 V
- + N or CMF + N + CMF
420 V < U
N
< 500 V Standard:
Û
LL
= 1300 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced:
Û
LL
= 1600 V,
0.2
microsecond
rise time
- + N or CMF + N + CMF
500 V < U
N
< 600 V Reinforced:
Û
LL
= 1600 V
+ du/dt + du/dt + du/dt + N + LCMF
or
Reinforced:
Û
LL
= 1800 V
- + N or CMF + N + CMF
600 V < U
N
< 690 V Reinforced:
Û
LL
= 1800 V
+ du/dt + du/dt + du/dt + N + LCMF
Form-wound U
N
< 690 V Reinforced:
Û
LL
= 2000 V,
0.3
microsecond
rise time
n.a. + N + CMF + N + CMF

Table of Contents

Other manuals for ABB ACS 600 MultiDrive

Related product manuals