ACS 600 MultiDrive Technical Data
A-34 ACS 600 MultiDrive
NIOC Board
Specifications
Data of the external control connection board NIOC-01 of the ACS 600
product family are given below. NIOC-01 board is included in the drive
section of the ACS 600 MultiDrive. For external control connections of
the supply section, refer to Diode/Thyristor/IGBT Supply Sections
Users Manual. For external control connections of the control section,
refer to Common Drive Control Manuals.
ACS/ACC/ACP 600, ACS 600 MultiDrive
NIOC-01 Board
Analogue Inputs
The advantage of the differential
analogue input is that the earth
potential of the device or
transmitter sending an analogue
signal can differ up to ± 15 V from
the earth potential of the ACx 600
chassis without disturbing the
signal. Differential input also
efficiently attenuates common
mode disturbances coupled to
control cables.
ACS 600, ACS 600 MultiDrive: Two Programmable Differential Current Inputs:
0 (4) to 20 mA, R
in
= 100 W
ACC 600: Two Differential Current Inputs: 0 to 20 mA, R
in
= 100 W
ACP 600: One Programmable Differential Current Input: 0 to 20 mA, R
in
= 100 W
ACS/ACP 600, ACS 600 MultiDrive: One Programmable Differential Voltage
Input: ACS 600: 0 (2) to 10 V, R
in
> 200 kW; ACP 600: 0 to 10 V, R
in
> 200 kW
ACC 600: One Differential Voltage Input: 0 to 10 V, R
in
> 200 kW
Common Mode Voltage:
± 15 VDC, max.
Common Mode Rejection Ratio: >
60 dB at 50 Hz
Resolution: 0.1 % (10 bit)
Inaccuracy:
± 0.5 % (Full Scale Range) at 25 °C. Temperature Coefficient:
± 100 ppm/°C, max.
Input Updating Time: 12 ms (ACS 600), 44 ms (ACC 600), 1 ms (ACP 600), 10 ms
(ACS 600 MultiDrive)
Constant Voltage Output Voltage: 10 VDC ± 0.5 % (Full Scale Range) at 25 °C. Temperature Coefficient:
± 100 ppm/°C, max.
Maximum Load: 10 mA
Applicable Potentiometer: 1 kW to 10 kW
Auxiliary Power Output Voltage: 24 VDC ± 10 %, Short circuit proof
Maximum Current: 250 mA or 130 mA with NLMD-01 option
Analogue Outputs ACS/ACC 600, ACS 600 MultiDrive: Two Programmable Current Outputs: 0 (4)
to 20 mA, R
L
< 700 W
ACP 600: One Programmable Current Output: 0 to 20 mA, R
L
< 700 W
Resolution: 0.1 % (10 bit)
Inaccuracy:
± 1 % (Full Scale Range) at 25 °C. Temperature Coefficient:
± 200 ppm/°C, max.
Output Updating Time: 24 or 100 ms (ACS 600), 44 ms (ACC 600), 8 ms
(ACP 600), 10 ms (ACS 600 MultiDrive)