ACS 600 MultiDrive Technical Data
ACS 600 MultiDrive A-29
Power Cable Entries
Notes concerning the cable entry tables are below.
Tightening Torque Tightening torques for screw connections (applicable to zinc and
chrome platings and screw strength class 8.8) are presented below.
* valid also for greased screws
Marking Below is explained the way cable connections are marked in the
following tables. The terminals accept cable lugs according to
DIN 46234 for copper cables and DIN 46329 for aluminium cables.
Screw Torque (Nm) *
Soft aluminium Alloyed aluminium and copper
M5 3.5 3.5
M6 6 9
M8 17 20
M10 35 40
M12 55 70
M16 130 180
4x(13x18)
Number of connection
Connection hole (max. screw) diameter or
holes in terminal
Note: Cable lugs can also be fastened using screws one size down from the hole
size. Example: A cable lug with a hole diameter of 12.5 mm can be fastened with
either a M12 or a M10 bolt.