ACS 600 MultiDrive Technical Data
ACS 600 MultiDrive A-19
Cabinet
The cabinet, degrees of protection and free space requirements of
ACS 600 MultiDrive are listed below.
1)
IP 21 = standard, R = air outlet duct
2)
200 between cabinets when installed back to back
IP 54 R Air Outlet Duct
Connection
The dimensions of the duct adjoining to IP 54 R cabinet are below.
ACx 600 Type Enclosure Degree of
Protection
Space
above
mm
Space
below
mm
Space on
left/right
mm
Space in
front/back
mm
ACS 600 MultiDrive Cabinet
IP 21, IP 22, IP 42,
IP 54 R
1)
500 0 0 200/100
2)
Cabinet Width
mm
Duct Ø
mm
400 250
600 310
800 310
1000 2x310
1500 3x310
Common Cabinet Door Opening