ACS 600 MultiDrive Technical Data
ACS 600 MultiDrive A-23
Derating factor for degree of protection IP 21/22/42:
Above +40 °C, the rated output current is decreased 1.5 % for every additional
1 °C (up to +50 °C).
Example 1. If the ambient temperature is 50 °C the derating factor is
100 % - 1.5 · 10 °C = 85 % or 0.85. The output current is then 0.85 · I
2N
(or
I
2base
or I
2max)
.
Derating Diagram: the effect of ambient temperature on the ACS 600 MultiDrive
continuous load capacity.
%
°C
100
95
85
80
90
36
40
Current (%)
T (°C)44
48
52
-1.5 % per each + °C
IP 21/22/42
IP 54R