Appendix A – ACS/ACC/ACP 601 Technical Data
ACS/ACC/ACP 601 Frequency Converters A-19
Cooling Air Flow
Requirements
Cooling air flow requirements are given below.
( ) with
I
2Nsq
rating typically
Cooling Air Duct
Heat dissipations and cooling air flows of ACx 601 in a cooling air duct
installation are below.
ACx 601
Flow
Heat
Dissipation
ACx 601
Flow
Heat
Dissipation
ACx 601
Flow
Heat
Dissipation
m
3
/h ft
3
/h W BTU/Hr m
3
/h ft
3
/h W BTU/Hr m
3
/h ft
3
/h W BTU/Hr
-0005-3 40 1413 80 273 -0006-5 40 1413 100 341 -0009-6 60 2119 130 444
-0006-3 40 1413 100 341 -0009-5 40 1413 130 444 -0011-6 60 2119 170 581
-0009-3 40 1413 130 444 -0011-5 40 1413 170 581 -0016-6 60 2119 240 820
-0011-3 60 2119 170 581 -0016-5 60 2119 240 820 -0020-6 60 2119 320 1093
-0016-3 60 2119 240 820 -0020-5 60 2119 320 1093 -0025-6 70 2472 390 1332
-0020-3 70 2472 390 1332 -0025-5 70 2472 460 1571 -0030-6 100 3531 460 1571
-0025-3 100 3531 460 1571 -0030-5 100 3531 620 2117 -0040-6 260 9182 620 2117
-0030-3 260 9182 620 2117 -0040-5 260 9182 760 2596 -0050-6 260 9182 760 2596
-0040-3 260 9182 760 2596 -0050-5 260 9182 920 3142 -0060-6 280 9888 920 3142
-0050-3 260 9182 920 3142 -0060-5 260 9182 1130 3859 -0070-6 280 9888 1130 3859
-0060-3 280 9888 1130 3859 -0070-5 280 9888 1530 5225 -0100-6 660 23308 1530 5225
-0070-3 280 9888 1530
(1230)
5225
(4201)
-0100-5 280 9888 1840
(1700)
6284
(5806)
-0120-6 660 23308 1840 6284
-0100-3 660 23308 1840 6284 -0120-5 660 23308 2250 7684
-0120-3 660 23308 2250
(2240)
7684
7650
-0140-5 660 23308 2700 9221
Degree of
protection
Heat Dissipation Degree of
protection
Cooling Air Flow Out
Heatsink Front Section Heatsink Front Section
IP 22 85 % of
ACx 600 losses
15 % of
ACx 600 losses
IP 22 80 % of air flow 20 % of air flow
IP 54 90 % of
ACx 600 losses
10 % of
ACx 600 losses
IP 54 100 % of air flow 0 % of air flow