Ambient conditions, storage
Ambient storage conditions refer to the conditions du/dt filters are subjected to
during storage in the protective package.
Temperature: -40 to +70
°C.
Relative humidity: Less than 95%, no condensation allowed
Atmospheric pressure: 70 to 106 kPa
Vibration:
AOCH0xxx-70: Max 1 mm (5 to 13.2 Hz), max 7 m/s
2
(13.2 to 100 Hz) sinusoidal
(IEC 60068-2)
NOCH0xxx-6x: Max 0.3 mm (2 to 9 Hz), max 1 m/s
2
(9 to 200 Hz) sinusoidal (IEC
60068-2)
Shock: Max 100 m/s
2
, 11 ms (IEC 60068-2-27)
Ambient conditions, transportation
Ambient transportation conditions refer to the conditions du/dt filters are subjected to
during transportation in the protective package.
Temperature: -40 to +70
°C
Relative humidity: Less than 95%, no condensation allowed.
Atmospheric pressure: 60 to 106 kPa
Vibration: Max 3.5 mm (2 to 9 Hz), max 15 m/s
2
(9 to 200 Hz) sinusoidal (IEC
60068-2)
Shock: Max 100 m/s
2
, 11 ms (IEC 60068-2-27)
Bump: Max 300 m/s
2
, 6 ms (IEC 60068-2-29)
Free fall: 250 mm